Inductance in Transmission Line

💡
Key learnings:
  • Definition of Inductance: Inductance in a transmission line is the property that causes it to oppose changes in current, due to the magnetic flux created by the current.
  • Flux Linkage: Flux linkage in a conductor involves the interaction of magnetic flux with the current, influencing inductance.
  • Internal and External Inductance: Internal inductance is due to flux within the conductor, while external inductance arises from flux outside the conductor.
  • Two-Wire System Inductance: The inductance in a two-wire single-phase system depends on the currents in both wires and their distance apart.
  • Three-Phase System Inductance: In a three-phase transmission line, the inductance is influenced by the currents in all three conductors and their mutual interactions.

Reason of Transmission Line Inductance

AC electric power travels on a transmission line at high voltage and current. That alternating current in a conductor produces alternating magnetic flux. Neighbouring parallel conductors then share that flux. Flux links a conductor both inside it and outside it. Internal linkage comes from the conductor’s own current. External linkage comes from flux outside the surface. The term inductance is the flux linkage λ per ampere. For a coil of N turns linked by flux Φ from current I,


For a transmission line N = 1. Only the flux Φ is needed, and that value gives the line inductance.

Calculation of Inductance of Single Conductor

Calculation of Internal Inductance due to Internal Magnetic Flux of a Conductor

Consider a conductor carrying current I along its length l. Let x be the variable internal radius, and r the original radius of the conductor. The cross-sectional area for radius x is πx2 square units, with current Ix flowing through it. The value of Ix can be expressed in terms of the original current I and the cross-sectional area πr2 square units.

inductance of single conductor

Now, consider a small thickness dx along a 1m length of the conductor, where Hx is the magnetizing force due to current Ix in the area πx2.

And magnetic flux density Bx = μHx, where μ is the permeability of this conductor. Again, µ = µ0µr. If it is considered that the relative permeability of this conductor µr = 1, then µ = µ0. Hence, here Bx = μ0 Hx.

dφ for small strip dx is expressed by

Here entire cross-sectional area of the conductor does not enclose the above expressed flux. The ratio of the cross sectional area inside the circle of radius x to the total cross section of the conductor can be thought about as fractional turn that links the flux. Therefore the flux linkage is

Now, the total flux linkage for the conductor of 1m length with radius r is given by

Hence, the internal inductance is

External Inductance due to External Magnetic Flux of a Conductor

Assume that due to the skin effect, current I is concentrated near the conductor’s surface. Consider y as the distance from the center, representing the external radius of the conductor.
external inductance due to external magnetic flux of a conductor
Hy is the magnetizing force and By is the magnetic field density at y distance per unit length of the conductor.

Let us assume magnetic flux dφ is present within the thickness dy from D1 to D2 for 1 m length of the conductor as per the figure.

As the total current I is assumed to flow in the surface of the conductor, so the flux linkage dλ is equal to dφ.

But we have to consider the flux linkage from conductor surface to any external distance, i.e. r to D



Inductance of Two Wire Single Phase Transmission Line

Suppose conductor A of radius rA carries a current of IA in opposite direction of current IB through the conductor B of radius rB. Conductor A is at a distance D from conductor B and both are of length l. They are in close vicinity with each other so that flux linkage takes place in both of the conductors due to their electromagnetic effects.
two wire single phase

Let us consider the magnitude of current in both conductors are same and hence IA = – IB,
Now, total flux linkage in conductor A = flux linkage by self-current of conductor A + flux linkage on conductor A due to current in the conductor B.
Similarly, flux linkage in conductor B = flux linkage by self-current of conductor B + flux linkage on conductor B due to current through conductor A.
flux of two wire single phase
Now if we consider a point P in close vicinity both conductor A and B, the flux linkage at point P would be, flux linkage at point P for current carrying conductor A + flux linkage at point P for current carrying conductor B i.e.

Now, ……… shown in the figure below in figure (a) and (b).

  • λAAP is the flux linkage at point P for conductor A due to current through conductor A itself.
  • λABP is the flux linkage at point P for conductor A due to current through conductor B.
  • λBAP is the flux linkage at point P for conductor B due to current through conductor A.
  • λBBP is the flux linkage at point P for conductor B due to current through conductor B itself.



λABP and λBAP are negative in value because the directions current are opposite with respect to each other.

If we consider that both conductor are with same radius, i.e. rA = rB = r and point P is shifted to infinite distance then we can write that


If conductor A becomes bundled conductor, then its geometrical mean radius (GMR) will be calculated for n number of conductors per bundle.

Where, d is the distance between the central axis of conductors within the bundle.

Inductance in Three Phase Transmission Line

In the three phase transmission line, three conductors run parallel to each other. In a balanced set the current in each conductor has the same magnitude and a 120° phase shift.

Let us consider conductor A produces magnetic flux φA,
Conductor B produces magnetic flux φB,
And conductor C produces magnetic flux φC.
When they carry the current of the same magnitude “I”, they are in flux linkage with each other.
three phase transmission line
Now, let us consider a point P near three conductors. So, flux linkage at point P due to current through conductor A is,

Flux linkage at point P for conductor A due to current through conductor A =

Flux linkage at point P for conductor A due to current through conductor B =
Flux linkage at point P for conductor A due to current through conductor C =
Therefore, flux linkage at point P for conductor A,

As, and in balanced system, then we can write that




If we arrange them in matrix form, then we get

Where, λA, λB, λC are the total flux linkages of conductor A, B and C.
LAA, LBB and LCC are the self inductances of conductor A, B and C.
LAB, LAC, LBC, LBA, LCA, LCB are the mutual inductances of between conductors A, B and C.

Again balanced system

And

In balanced system, then we can write that


Similarly,