
- Three-phase Transformer Connections Definition: A three-phase transformer connects its primary and secondary windings in star or delta configurations for various electrical applications.
- Star Connection: In star connection, three windings connect at one end to form a neutral point, used for creating a neutral terminal.
- Delta Connection: In delta connection, windings form a closed loop, creating a triangle-like shape, providing a path for the supply to the junction points.
- Types of Connections: Three-phase transformers can connect in Delta-Delta, Star-Star, Delta-Star, and Star-Delta configurations, each with specific voltage and current characteristics.
- Open Delta Connection: This connection operates with two transformers, maintaining three-phase power with a lower load capacity when one transformer is out of service.
What is a Transformer Connection?
A three-phase transformer connects each three-phase winding in star (Y) or delta (Δ). The primary and secondary choices together set the voltage ratio, the phase shift and whether a neutral is available.
The bank can be three single-phase units or one three-limb (or five-limb) core. One three-phase core uses less iron and copper than three separate units of the same rating.
Generation, transmission and distribution are three-phase. Three-phase transformers step that voltage up or down.
Three-phase Connections
Each winding is connected in one of two ways:
- Star connection
- Delta connection
Star Connection
In a star (Y, wye) connection, one end of each of the three windings joins at a common point. That point is the star or neutral point. A neutral conductor can be taken from it.
The free ends are the three line terminals. The diagram looks like a Y, so it is also called a Y-connection or wye connection.
The star connection is shown in the figure below.

Delta Connection
In a delta (Δ) connection the three windings form a closed loop. The three line conductors join the three corners. There is no star point.
The loop looks like the Greek letter delta, so it is called a delta or mesh connection.
The delta connection is shown in the figure below.

Factors Affecting Choice of Connection
Choice of star or delta depends on:
- a neutral for grounding and single-phase loads
- a path for zero-sequence current and third harmonic current
- voltage to earth and insulation class
- phase shift if units must run in parallel
- copper, iron and bushing cost
- behaviour on earth faults and open-phase faults
Three Phase Voltages and Currents in Star and Delta Connection
Line voltage is the voltage between two lines. Phase (winding) voltage is the voltage across one winding. In star, that winding voltage is also the line-to-neutral voltage.
In star, line current equals winding current. Each line feeds only one winding.
![]()
On a four-wire star as in the figure, Kirchhoff’s law around two phase voltages 120° apart gives a line voltage of √3 times the line-to-neutral voltage.
![]()
In delta there is no neutral. Line voltage equals winding (phase) voltage. The stored latex still writes V_LN for that winding voltage.
![]()
Three Phase Transformer Connections
Each three-phase transformer has a primary winding set and a secondary winding set.
Each set can be star or delta. The usual four combinations are:
- Delta-Delta (Δ-Δ)
- Star-Star (Y-Y)
- Delta-Star (Δ-Y)
- Star-Delta (Y-Δ)
The first letter is the primary. The second letter is the secondary.
Delta-Delta (Δ-Δ) Connection
In a delta-delta bank both windings are delta. The connection is shown below.

Primary ends are A1A2, B1B2 and C1C2. Secondary ends are a1a2, b1b2 and c1c2.
A1 and a1 have the same polarity. Winding A1A2 pairs with a1a2.
The phasor diagram below is for lagging power factor cos ф. Magnetizing current and leakage-impedance drops are omitted.

On each delta, line voltage equals winding voltage. Primary line voltages VAB, VBC and VCA are in phase with Vab, Vbc and Vca (Dd0). The voltage ratio equals the turns ratio.
![]()
With balanced load, line current is √3 times winding current. Neglecting magnetizing current, the current ratios are:
![]()
Primary and secondary voltages are in phase, so this is a 0° (Dd0) connection.
Reverse the secondary delta (swap the sense of each winding) and the voltages are 180° apart: a Dd6 connection.
The 180° wiring and phasors are shown below.

Here secondary corners b1c2, c2a2 and a1b2 are joined. The phasors show secondary voltage opposite to primary voltage.
Delta-delta is used when:
- It can supply a balanced or unbalanced three-phase load (no single-phase-to-neutral load).
- Triplen harmonics circulate inside the delta and do not appear in the line-to-line voltage.
- If one unit of a three-unit bank is lost, the other two can run as an open-delta (V-V) bank at reduced rating.
There is no neutral, so this bank is not used where a line-to-neutral load or a grounded-wye source is required on that winding.
Star-Star (Y-Y) Connection
In a star-star (Y-Y) bank both windings are star. The connection is shown below.

Line current equals winding current. Line voltage is √3 times phase voltage. With magnetizing current ignored, the voltage phasors look like the 0° delta-delta set.
For an ideal transformer the voltage ratio is
![]()
The current ratio is
![]()
With no neutral conductor, an unbalanced load shifts the star point and the phase voltages go unequal. Ungrounded Y-Y is a poor choice for unbalanced load.
Y-Y is also sensitive to the third-harmonic part of magnetizing current.
Magnetizing current is not a sine wave: it includes a triplen (third-harmonic) component. A closed path for that current is needed if the flux is to stay close to a sine wave.
The three triplen magnetizing currents are in phase with each other. They add at the star point instead of cancelling.
If the star points are isolated, those currents have no return path. The flux picks up a third-harmonic component and both windings show a third-harmonic voltage to earth.
That extra voltage sits on the fundamental. In textbook sketches the peak can approach about twice the usual value. The exact peak depends on core saturation and whether the star point is grounded.
Two common fixes are:
Solid Grounding of Neutral
Solidly earth the primary star point to the source neutral. The triplen magnetizing current can then flow in the neutral and the large third-harmonic voltage is avoided.
The same conductor also returns unbalanced load current.
The neutral then carries 150 Hz (or 180 Hz) current, which can couple into nearby communication circuits.
Provide Tertiary Winding
If you cannot run a neutral, add a third winding on the same core: a tertiary.
That tertiary is connected in delta. The bank is then Y-Δ-Y: the closed delta gives a path for triplen current without a neutral conductor.
Delta-Star (Δ-Y) Connection
In a delta-star (Δ-Y) bank the primary is delta and the secondary is star.
The connection is shown below.

On the delta primary, line voltage equals winding voltage.
On the star secondary, line voltage is √3 times phase voltage.
The line-to-line voltage ratio is then:
![]()
![]()
![]()
The phasors below are for lagging power factor and balanced load.

Secondary phase voltage VaN leads primary VAN by 30°. VbN and VcN lead VBN and VCN, by the same angle. IEC vector group Dy11 is this +30° case.
Reverse one winding set and the secondary lags the primary by 30° (Dy1). That wiring is shown below.

Star-Delta (Y-Δ) Connection
In a star-delta (Y-Δ) bank the primary is star and the secondary is delta. The connection is shown below.

Star primary: line voltage is √3 times phase voltage. Delta secondary: line voltage equals winding voltage.
The line-to-line voltage ratio is:
![]()
![]()
The phasors are the Δ-Y set with primary and secondary swapped. Line voltages are shifted 30°. Yd11 is the +30° case.
Reverse one winding set for a 30° lag (Yd1). That wiring is shown below.

Y-Δ is Δ-Y with the windings swapped. Either bank can feed an unbalanced three-phase load. The delta gives a path for triplen current.
The delta holds the Y-side voltages in balance for triplen magnetizing current and lets those harmonics circulate without a neutral conductor.
Open Delta Connection (V-V Connection)
If one unit of a delta-delta three-unit bank is lost, the other two can still feed a three-phase load at reduced rating. That emergency bank is an Open Delta connection (V-V).
Only two transformers are in circuit.
The open-delta connection is shown below.

Primary line voltages are VAB, VBC and VCA. The two remaining secondaries give Vab and Vbc. There is no winding from a to c, yet a voltage still appears between a and c.
![]()
(1) ![]()
Write the primary line voltage as VP and the secondary as VS.
![]()
![]()
![]()
Take leakage impedance as zero so the secondary voltages follow the primary angles.
![]()
![]()
Put those phasors into the stored equation:
![]()
![]()
![]()
![]()