- Shunt Reactor Definition: A shunt reactor is used to neutralize excess capacitive reactive power on long electrical transmission lines.
- Core Features: The core of a shunt reactor is specially designed with gaps to minimize energy losses and enhance efficiency.
- Cooling Efficiency: Utilizing an ONAN cooling system, the shunt reactor maintains operational temperatures effectively without requiring complex machinery.
- Safety Mechanisms: Equipped with pressure relief devices and Buchholz relays, shunt reactors ensure robust safety by monitoring and reacting to internal changes.
- Monitoring Systems: Advanced indicators like winding and oil temperature gauges help in the precise management of reactor conditions, preventing overheating.
A Shunt Reactor is used to compensate the capacitive reactive power of a long transmission line. The constructional features of a shunt reactor may vary from manufacturer to manufacturer, but the basics of construction are more or less the same.
Core of Shunt Reactor
Shunt reactors typically use a gapped core, built from Cold Rolled Grain Oriented Silicon Steel to cut down on hysteresis losses. The steel sheets are laminated to lessen eddy current losses. Radial gaps, placed by high electrical modulus spacers between lamination packets, enhance efficiency. Typically, a 5-limb, 3-phase core structure in a shell form is employed, where only the three inner limbs are gapped.
Winding of Shunt Reactor
There is nothing special about the winding of a reactor. It is mainly made of copper conductors. The conductors are paper insulated. Insulated spacers are provided between turns to maintain paths for oil circulation. This arrangement helps with efficient cooling of the winding.
Cooling System of Reactor
The ONAN (Oil Natural Air Natural) cooling system, sufficient for even high-voltage shunt reactors due to their low current operation, employs a radiator bank linked to the main tank for enhanced cooling.
Tank of Reactor
For UHV and EHV systems, the main tank, often a bell tank type, is crafted from thick steel sheets welded together to endure both full vacuum and atmospheric pressure. These tanks are also designed for easy transport by road and rail.
Conservator of Reactor
Conservator is provided at the top of the tank with main tank to conservator connecting pipe line of suitable diameter. The conservator is generally horizontally aligned cylindrical tank, to provide adequate space to the oil for expansion due to temperature rise. Flexible separator between air and oil or air cell is provided in the conservator for the said purpose. The conservator tank is also equipped with a magnetic oil gauge to monitor the oil level in the reactor. The magnetic oil gauge also gives an alarm through a normally open (NO) DC contact, attached to it when oil level falls below a preset level due to oil leakage or any other reason.
Pressure Relief Device
Due to a large fault inside the reactor, the oil inside the tank may suddenly and excessively expand. This huge oil pressure generated in the reactor should be released immediately along with separation of the reactor from the live power system. The Pressure Relief Device does this job. It is a spring loaded mechanical device fitted on the roof of the main tank. When the device actuates, the upward pressure of the oil in the tank becomes greater than the downward spring pressure; as a result, an opening appears in the valve disc of the device through which the expanded oil comes out to relieve the pressure formed inside the tank. There is a mechanical lever attached to the device which is normally in a horizontal position. When the device is actuated, this lever becomes vertical. By observing the alignment of the lever even from ground level, one can predict whether the Pressure Relief Device (PRD) has operated or not. The PRD is accompanied with a trip contact to trip the shunt reactor when the device actuates.
N B: PRD or such type of device cannot be reset remotely once it has actuated. It can only be reset manually by moving the lever back to its original horizontal position.
Buchholz Relay
One Buchholz relay is fitted across the pipe connecting the conservator tank and the main tank. This device collects gases generated in the oil and actuates the alarm contact attached to it. It also has a trip contact which is actuated at the event of sudden accumulation of gas in the device or rapid flow of oil (oil surge) through the device.
Silica Gel Breather
When oil becomes hot, it expands, so air from the conservator or air shell (where an air shell is used) comes out. During contraction of the oil, air from the atmosphere enters the conservator or air shell. This process is called breathing of the oil immersed equipment (like transformer or reactor). During breathing, moisture can enter the equipment if it is not taken care of. A pipe from the conservator tank or air shell is fitted with a container filled with silica gel crystal. When air passes through it, the moisture is absorbed by the silica gel.
Winding Temperature Indicator
Winding temperature indicator is a kind of indicating meter associated with a relay. It consists of a sensor bulb placed in an oil filled pocket on the roof of the reactor tank. There are two capillary tubes between the sensor bulb and the instrument housing. One capillary tube is connected to the measuring bellow of the instrument. The other capillary tube is connected to the compensating bellow fitted in the instrument. The measuring system, i.e. sensor bulb, both capillary tubes and both bellows, is filled with a liquid which changes its volume when temperature changes. The pocket in which the sensor bulb is immersed is surrounded by a heating coil which is fed by a current proportional to the current flowing through the winding of the reactor. Gravity operated NO contacts are attached to the pointer system of the instrument to provide a high temperature alarm and trip respectively.
Oil Temperature Indicator
The oil temperature indicator, featuring a sensor bulb in an oil-filled pocket at the reactor tank’s hottest point, uses two capillary tubes to link the sensor with the instrument’s measuring and compensating bellows. These components are filled with a liquid that expands or contracts with temperature changes, providing accurate temperature readings.
Bushing
The winding terminals of each phase come out from the reactor body through an insulated bushing arrangement. In a high voltage shunt reactor, the bushings are oil filled. The oil is sealed inside the bushing, which means there is no link between the oil inside the bushing and the oil inside the main tank. An oil level gauge is provided on the expansion chamber of the condenser bushings.