Insulation Coordination in Power System

💡
Key learnings:
  • Insulation Coordination Defined: Insulation coordination is the strategic arrangement of electrical insulation to minimize system damage and ensure easy repairs in case of failure.
  • System Voltages: Understanding nominal and maximum system voltages is crucial for designing a power system’s insulation to handle different operational conditions.
  • Earthing Factor: The earthing factor determines how well a system is grounded, influencing its ability to manage faults and maintain stability.
  • Protective Devices: Surge arrestors and other protective devices are essential for maintaining safe voltage levels and preventing equipment damage during voltage spikes.
  • Economic Efficiency: Insulation coordination must balance technical requirements with economic feasibility, especially at higher voltage levels.

Insulation Coordination in Power System is the process of selecting equipment insulation levels that can withstand the expected electrical stresses in an electrical power system. The study considers overvoltage sources, protective devices, equipment characteristics, installation geometry, environment and an acceptable risk of failure of insulator.
An overvoltage can stress several insulation paths. Its effect depends on the travelling wave, equipment location, surge-arrester separation and grounding. Coordination does not rely on one deliberately weak point.

Insulators and equipment have different withstand characteristics and consequences of failure. Insulation coordination seeks a rational balance between withstand level, protective-device performance, failure probability, service continuity and cost. Protective gaps may be intentional in some designs, but the general objective is to keep stresses below the selected withstand levels with the required statistical confidence.
The following insulation coordination terms explain that selection process.

Nominal System Voltage

Nominal System Voltage is the phase-to-phase voltage used to designate a three-phase system. Examples include 11 kV, 33 kV, 132 kV, 220 kV and 400 kV. It is a system label rather than the voltage present at every instant.

Maximum System Voltage

Maximum System Voltage is an older term for the highest phase-to-phase power-frequency voltage expected under normal operating conditions. Current equipment standards use the highest voltage for equipment, Um, to associate standard withstand levels with an installation.
The frozen table pairs example nominal system voltage values with corresponding maximum system voltage values. The applicable standard and equipment rating must be checked for a real project.

Nominal System Voltage in KV113366132220400
Maximum System Voltage in KV123672.5145245420

NB – The percentage difference in this table is descriptive, not a general design rule. Standardised Um values are selected from the applicable voltage and equipment standards.

Factor of Earthing

The factor of earthing is the ratio of the highest power-frequency phase-to-earth voltage on a healthy phase during an earth fault to the phase-to-phase power-frequency voltage at the same location before the fault. Both values are rms quantities.
The ratio describes how the network earthing affects temporary overvoltage at the selected fault location.

Effectively Earthed System

Some standards and legacy practice call a location effectively earthed when its factor of earthing does not exceed 0.8. The governing grid code or equipment standard should define the term for a project.
An ideal solidly earthed system approaches 1/√3, or 0.577. An isolated-neutral system can approach 1.0 during a single earth fault, but actual values depend on network impedances.

Insulation Level

Equipment insulation may face lightning impulses, switching impulses and short duration power frequency over voltages during service. A selected withstand level accounts for the type, magnitude, duration and probability of each relevant stress. The short duration power frequency over voltages also affect surge-arrester selection and temporary-overvoltage duties. The resulting insulation level uses standard rated withstand voltages for the equipment class.
Depending on Um and the equipment standard, the selected set can include a lightning impulse withstand voltage, a short duration power frequency withstand voltage and a switching impulse withstand voltage. The choice follows IEC 60071 and the relevant apparatus standard, not a universal 300 kV threshold.

Lightning Impulse Voltage

A standard full lightning impulse voltage test uses a 1.2/50 µs waveform to represent a fast-front stress. It is a defined laboratory waveform, not the inevitable shape of a surge after travelling along a transmission line. A flashover or protective gap can chop an impulse, while real lightning surges vary with the stroke, line geometry, reflections and equipment. Test standards define full and chopped impulse procedures for the relevant apparatus. A lightning impulse voltage rating states the prescribed withstand test level.

Switching Impulse

Network energisation, fault clearing and other switching events can produce slow-front overvoltages. A standard Switching impulse is a unidirectional laboratory test waveform with a slower front and longer duration than the standard lightning impulse. Actual switching transients can be oscillatory and require system studies.

Short Duration Power Frequency Withstand Voltage

Short duration power frequency withstand voltage is the prescribed rms value of a sinusoidal power-frequency test voltage that equipment must withstand for the duration set by its standard. One minute is common, but it is not universal.

Protection Level Voltage of Protective Device

A metal-oxide surge arrester, sometimes called one of the lightning arrestors, conducts surge current and limits voltage at its terminals. Its protective level depends on discharge current, waveform and arrester characteristics. Equipment can see a higher voltage because of connecting-lead inductance, separation distance and travelling-wave effects, so arrester placement and grounding form part of the coordination study.

The following sections outline shielding, protective-device coordination and statistical study methods.

Using Shield Wire or Earth Wire

shield wire


An overhead shield wire intercepts many strokes that would otherwise reach a phase conductor. Its position, connection to each transmission tower and the structure grounding affect performance. Shielding reduces risk but cannot prevent every direct strike or backflashover. Substation masts and wires similarly reduce direct-stroke exposure of an electrical substation; they do not replace surge arresters or insulation coordination.

Conventional Method of Insulation Coordination

insulation coordination


A deterministic study compares the calculated representative overvoltage with the protective level of lightning arrestors and the equipment’s coordination withstand voltage. It includes arrester tolerance, distance effects, environmental corrections and modelling uncertainty. The selected standard withstand voltage then provides the required coordination margin.
There is no universal 15% to 25% margin. The applicable standard, stress shape, apparatus and study assumptions set the margin.

Statistical Methods of Insulation Coordination

insulation coordination


A statistical method models the probability distributions of overvoltage stress and insulation strength. It estimates a failure risk rather than applying a single fixed margin. Detailed simulations can include lightning and switching events, arrester behaviour, equipment location, atmospheric correction and system topology. Air-clearance and string-length design does not follow one universal V1.6 rule. The accepted risk, standard withstand series and cost determine the final insulation level.

Want To Learn Faster? 🎓
Get electrical articles delivered to your inbox every week.
No credit card required—it’s 100% free.

About Electrical4U

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

Leave a Comment