- Air Circuit Breaker Definition: An air circuit breaker is a type of electrical protection device that uses air to extinguish arcs, preventing damage from excess current in electrical circuits.
- Operation Mechanism: Air circuit breakers interrupt current by increasing arc voltage through methods like cooling the arc, extending the arc path, or dividing it into several series arcs.
- Types of ACB: There are mainly two types, plain air circuit breakers and air blast circuit breakers, with the latter used in high voltage systems for their rapid operation capabilities.
- Advantages of Air Blast Circuit Breakers: These include a lack of fire hazard, faster operation, extended contact life, and reduced maintenance needs compared to other types.
- Usage and Applications: While older for medium voltage, air circuit breakers remain preferred for certain low voltage applications and in specific geographic regions due to their safety features and reliability.
What is Air Circuit Breaker?
An Air Circuit Breaker (also known as an Air Blast Circuit Breaker or ACB) is an automatically operated electrical switch that uses air to protect an electrical circuit from damage caused by excess current from an overload or short circuit. Its primary function is to interrupt current flow after a fault is detected. When this happens, an arc will appear between the contacts that have broken the circuit. Air circuit breakers use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air, thus blowing out the arc.
This type of circuit breaker operates in air at atmospheric pressure. After the development of the oil circuit breaker, the medium voltage air circuit breaker has been largely replaced by oil circuit breakers worldwide.
In countries like France and Italy, ACBs remain the preferred choice for systems up to 15 kV, mainly to mitigate the risk of oil fires associated with oil circuit breakers. In America, ACBs were commonly used for systems up to 15 kV before newer vacuum circuit breakers and SF6 circuit breakers were developed.
Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation. You can also have remote controlled circuit breaker which can be operated from a distance, whereas this is not the case with a fuse.
Working Principle of Air Circuit Breaker
The working principle of this breaker is rather different from those in any other types of circuit breakers. The main aim of all kind of circuit breaker is to prevent the reestablishment of arcing after current zero by creating a situation where in the contact gap will withstand the system recovery voltage.
The air circuit breaker operates uniquely by generating an arc voltage higher than the supply voltage to interrupting arc. Arc voltage, the minimum voltage needed to maintain an arc, is increased in three primary ways by this breaker.
- One method to increase the arc voltage involves cooling the arc plasma, reducing the mobility of particles within the plasma and requiring a higher voltage gradient to sustain the arc.
- It may increase the arc voltage by lengthening the arc path. As the length of arc path is increased, the resistance of the path is increased, and hence to maintain the same arc current more voltage is required to be applied across the arc path. That means arc voltage is increased.
- Splitting up the arc into a number of series arcs also increases the arc voltage.
Types of ACB
There are mainly two types of ACB are available.
- Plain air circuit breaker.
- Air blast Circuit Breaker.
Operation of ACB
The operation of an ACB can be broken down into three steps:
- The first objective is usually achieved by forcing the arc into contact with as large an area as possible of insulating material. Every air circuit breaker is fitted with a chamber surrounding the contact. This chamber is called ‘arc chute’. The arc is driven into it. If inside of the arc chute is suitably shaped, and if the arc can be made conform to the shape, the arc chute wall will help to achieve cooling. This type of arc chute should be made from some kind of refractory material. High temperature plastics reinforced with glass fiber and ceramics are preferable materials for making arc chute.
- The second objective that is lengthening the arc path, is achieved concurrently with fist objective. If the inner walls of the arc chute is shaped in such a way that the arc is not only forced into close proximity with it but also driven into a serpentine channel projected on the arc chute wall. The lengthening of the arc path increases the arc resistance.
- The third technique is achieved by using metal arc slitter inside the arc chute. The main arc chute is divided into numbers of small compartments by using metallic separation plates. These metallic separation plates are actually the arc splitters and each of the small compartments behaves as individual mini arc chute. In this system the initial arc is split into a number of series arcs, each of which will have its own mini arc chute. So each of the split arcs has its own cooling and lengthening effect due to its own mini arc chute and hence individual split arc voltage becomes high. These collectively, make the overall arc voltage, much higher than the system voltage.
This was working principle of air circuit breaker now we will discuss in details the operation of ACB in practice.
The air circuit breaker, operated within the voltage level 1 kV, does not require any arc control device. Mainly for heavy fault current on low voltages (low voltage level above 1 kV) ABCs with appropriate arc control device, are good choice. These breakers normally have two pairs of contacts.
The main pair of contacts carries the current at normal load and these contacts are made of copper. The additional pair is the arcing contact and is made of carbon. When circuit breaker is being opened, the main contacts open first and during opening of main contacts the arcing contacts are still in touch with each other.
As the current gets, a parallel low resistive path through the arcing contact during opening of main contacts, there will not be any arcing in the main contact. The arcing is only initiated when finally the arcing contacts are separated. The each of the arc contacts is fitted with an arc runner which helps, the arc discharge to move upward due to both thermal and electromagnetic effects as shown in the figure.

As the arc is driven upward it enters in the arc chute, consisting of splitters. The arc in chute will become colder, lengthen and split hence arc voltage becomes much larger than system voltage at the time of operation of air circuit breaker, and therefore the arc is quenched finally during the current zero.
Although these types of circuit breakers have become obsolete for medium voltage application, but they are still preferable choice for high current rating in low voltage application.
Air Blast Circuit Breaker
These types of air circuit breaker were used for the system voltage of 245 KV, 420 KV and even more, especially where faster breaker operation was required. Air blast circuit breaker has some specific advantages over oil circuit breaker which are listed as follows,
- There is no chance of fire hazard caused by oil.
- The breaking speed of circuit breaker is much higher during operation of air blast circuit breaker.
- Arc quenching is much faster during operation of air blast circuit breaker.
- The duration of arc is same for all values of small as well as high currents interruptions.
- As the duration of arc is smaller, so lesser amount of heat realized from arc to current carrying contacts hence the service life of the contacts becomes longer.
- The stability of the system can be well maintained as it depends on the speed of operation of circuit breaker.
- Requires much less maintenance compared to oil circuit breaker.
Despite their advantages, air blast circuit breakers also present several disadvantages:
- In order to have frequent operations, it is necessary to have sufficiently high capacity air compressor.
- Frequent maintenance of compressor, associated air pipes and automatic control equipments is also required.
- Due to high speed current interruption there is always a chance of high rate of rise of re-striking voltage and current chopping.
- There also a chance of air pressure leakage from air pipes junctions.
As we said earlier that there are mainly two types of ACB, plain air circuit breaker and air blast circuit breaker. But the later can be sub divided further into three different categories.
- Axial Blast ACB.
- Axial Blast ACB with side moving contact.
- Cross Blast ACB.
Axial Blast Air Circuit Breaker

In axial blast ACB the moving contact is in contact with fixed contact with the help of a spring pressure as shown in the figure. There is a nozzle orifice in the fixed contact which is blocked by tip of the moving contact at normal closed condition of the breaker. When fault occurs, the high pressure air is introduced into the arcing chamber.

The air pressure overcomes the spring pressure, retracting the moving contact from the fixed contact and opening the nozzle hole. Concurrently, high-pressure air flows through the nozzle, extending and cooling the arc, thus increasing the arc voltage above the system voltage, effectively quenching the arc as it cannot be sustained.
Axial Blast ACB with Side Moving Contact
In this type of axial blast air circuit breaker the moving contact is fitted over a piston supported over a spring. In order to open the circuit breaker the air is admitted into the arcing chamber when pressure reaches to a predetermined value, it presses down the moving contact; an arc is drawn between the fixed and moving contacts. The air blast immediately transfers the arc to the arcing electrode and is consequently quenched by the axial flow of air.
Cross Blast Air Circuit Breaker

The working principle of cross blast air circuit breaker is quite simple. In this system of air blast circuit breaker the blast pipe is fixed in perpendicular to the movement of moving contact in the arcing chamber and on the opposite side of the arcing chamber one exhaust chamber is also fitted at the same alignment of blast pipe, so that the air comes from blast pipe can straightly enter into exhaust chamber through the contact gap of the breaker.
The exhaust chamber is spit with arc splitters. When moving contact is withdrawn from fixed contact, an arc is established in between the contact, and at the same time high pressure air coming from blast pipe will pass through the contact gap and will forcefully take the arc into exhaust chamber where the arc is split with the help of arc splitters and ultimately arc is quenched.





