- Foundation Design Definition: The foundation design for transmission towers involves creating stable bases using RCC, designed to withstand various loads and soil conditions.
- Different Soil Types: Transmission tower foundations must adapt to different soil types like black cotton soil, fissured rock, and sandy soil, each requiring unique construction methods.
- Dry Fissured Rock: Foundations in dry fissured rock need special considerations like undercuts and anchor bars for stability.
- Stability Factors: Ensuring stability against sliding, overturning, and buoyancy is crucial, with specific safety factors for normal and short circuit conditions.
- Protective Measures: Additional protection for foundations is necessary in aggressive soils to prevent damage and ensure longevity.
Design of Foundation of Transmission Towers in Different Soils
- All foundation shall be of RCC. The design and construction of RCC structures shall be carried out as per IS:456 and minimum grade of concrete shall be M-20.
- Limit state method of design shall be adopted.
- Cold twisted deformed bars as per IS:1786 or TMT bars shall be used as reinforcement.
- Foundations shall be designed for the critical loading combination of the steel structure and or equipment and/or superstructure.
- Protection should be provided to foundations when needed, especially for aggressive soils like alkaline soil, black cotton soil, or any soil harmful to concrete foundations.
- All structures must be checked for stability against sliding and overturning during construction and operation under various load combinations.
- When checking for overturning, consider the weight of the soil above the footing, but do not include the inverted frustum of the earth on the foundation.
- Base slab of any underground enclosure shall also be designed for maximum ground water table. Minimum factor of safety of 1.5 against bouncy shall be ensured.
- Tower and equipment foundations must have a safety factor of 2.2 for normal conditions and 1.65 for short circuit conditions to prevent sliding, overturning, and pullout.
Guidelines for Classification of Foundations of Transmission Towers in Different Soils
A transmission tower foundation must suit the ground profile at its location. For an Power System transmission project, selection should use site investigation data, tower reactions, groundwater conditions, construction constraints and the governing standards. The table below records one legacy classification system for Foundations of transmission towers in different Soil conditions; it is not a substitute for a project-specific geotechnical design.
| SL | Name of soil encountered | Type of foundation to be adopted |
| 1 | In good soil (silty sand mixed with clay) | Normal Dry |
| 2 | Where top layer of Black Cotton soil extends upto 50% of the depth with good soil there after. | Partial Black Cotton |
| 3 | Where top layer of black cotton soil exceeds 50% and extends upto full depth or is followed by good soil. | Black Cotton |
| 4 | Where top layer is good soil upto 50% of the depth but the lower layer is a black cotton soil | Black Cotton |
| 5 | Where subsoil water is met at 1.5 ml or more below the ground level in good soil | Wet |
| 6 | Good soil locations which are in surface water for long period with water penetration not exceeding 1.0 m below ground level (e.g. paddy fields). | Wet |
| 7 | In good soil where subsoil water is encountered between 0.75m and 1.5m depth from ground level. | Partially submerged |
| 8 | In good soil where subsoil water is encountered within 0.75m depth from ground level | Fully Submerged |
| 9 | Where top layer of normal dry soil extends upto 85% of the depth followed by fissured rock without presence of water. | Dry Fissured Rock |
| 10 | Where top layer is lissured rock followed by good soil/sandy soil with/without presence of water | Special foundation |
| 11 | Where normal soil/tissured rock extends upto 85% of the depth followed by hard rock | Dry fissured Rock with under cut in Fisured Rock combined with anchor bar for hard rock design |
| 12 | Where fissure rock os encountered with subsoil water within 0.75m or below 0.75m from G.L. (Top layer may be either a good soil or black cotton soil) | Submerged Fissured Rock |
| 13 | Where Hard Rock is encountered at 1.5 m or less below ground level. | Hard Rock |
| 14 | Where Hard Rock is encountered from 1.5 m to 2.5m below G.L. (Top layer being good soil) | with chimney for Normal Soil Hard Rock Foundation |
| 15 | Where hard rock is encountered from 1.5m to 2.5 m below G./L. (Top layer either in Black cotton) soil or fissured Rock | Hard Rock Foundation design with chimneys designed for wet black cotton soil. |
| 16 | Where fissured rock is encountered at the bottom of pit (with black cotton soil at top) | Composite Foundation |
| 17 | Where hard rock is encountered at bottom with water and black cotton soil at top and hard rock layer depth is less than 1.5 m. | Hard Rock |
| 18 | Sandy soil with clay content not exceeding 10% | Dry Sandy soil foudation |
| 19 | Sandy soil with water table in the pits | Wet sandy soil design to be developed considering the depth of water |
| 20 | Where top layer upto 1.5 m below G.L. is normal dry soil and thereafter hard soil/murrum | Normal dry with undercut |
| 21 | Where bottom layer is marshy soil with top layer of good soil/fissured rock/black cotton | Soil investigation is to be carried out and special foundation design to be developed. |
| 22 | Where the top layers are a combination of clinker mixed with firm soil, gravel and stone chips upto 60% of foundation deapth from ground level followed by hard murrum | Normal dry with undercut |
| 23 | Where top layers are combination of hard murrum, soft rock etc. followed by yellow/black clayee soil | Special foundation design is to be developed after carrying out soil investigation. |
Soil profiles rarely fit a short classification table exactly. Where the listed descriptions do not match the site, a qualified geotechnical and structural design team should develop the foundation from the investigation results and project load cases.