01․ Incremental cost of two generators Ic1 = 0.2 P1+60, Ic2 = 0.3 P2+40 and the ratings of the generator are 150 and 250 MW. Find the load sharing of each generator for a load of 200 MW?
Given that
P1 + P2 = 200 MW
Optimum condition of economic load dispatch is
Ic1 = Ic2
0.2 P1 + 60 = 0.3 P2 + 40
0.2 P1 - 0.3 P2 = -20
By solving of above equations
P1 = 80 MW, P2 = 120 MW
02․ The Y bus matrix of 100 bus interconnected system is 90% sparse. Hence the number of transmission lines in the system must be
Total number of transmission lines
Where,
n = number of buses
x = sparsity

03․ A power system consists of 300 buses out of which 20 buses are generator buses, 25 buses are the ones with reactive power support buses and 15 buses are ones with fixed shunt capacitors. All the other buses are load buses. It is proposed to perform a load flow analysis for the system using Newton-Raphson Jacobian matrix is
Size of the Jacobian matrix = (2n-m-2)×(2n-m-2)
Where,
n = Total number of buses = 300
m = Total number of PV buses
m = Voltage control buses + Reactive power support buses + generator buses except slack bus = 44
Fixed shunt capacitors are supplying constant amount of reactive power, so that fixed shunt capacitors are considered as load buses or PQ buses.
Size of the Jacobian matrix = (2×300-44-2)×(2×300-44-2) = 554×554
04․ The Gauss Seidel load flow method has following disadvantages. Which of the following statement is wrong?
Advantages of gauss siedel method:
1. It is a simple algebraical equation, so that calculation time for each iteration is less.
2. More suitable for small size networks.
Disadvantages of gauss siedel method:
1. More number of iterations are required, so that it has slow convergence.
2. Initial approximate guessing value is required for convergence.
3. It required accelerating factor for convergence.
4. The choice of slack bus affects the convergence.
5. It is not applicable for the large power system networks.
05․ The incremental fuel costs for two generating units G1 and G2 are given by
Ic1 = 25 + 0.2 PG1 and Ic2 = 32 + 0.2 PG2, where PG1 and PG2 are real powers generated by the units. The economic allocation for a total load of 250 MW, neglecting transmission loss, is given by
Given that
P1 + P2 = 250 MW
Optimum condition of economic load dispatch is
Ic1 = Ic2
25 + 0.2 PG1 = 32 + 0.2 PG2
0.2 PG1 - 0.2 PG2 = 7
By solving of above equations
PG1 = 142.5 MW and PG2 = 107.5 MW
06․ A lossless power system has to serve a load of 250 MW. There are two generators(G1 and G2) in the system with cost curves C1 and C2 respectively defined as follows:
C1 = PG1+0.055P²G1
C2 = 3 PG2 + 0.03 P²G2
Where PG1 and PG2 are the MW injections from generators G1 and G2 respectively. Thus, the minimum cost dispatch will be
Given that
P1 + P2 = 250 MW........(1)
Optimum condition of economic load dispatch is
After solving of above equations
PG1 = 100 MW and PG2 = 150 MW
07․ A load centre is at an equidistant from the two thermal generating stations G1 and G2. The fuel cost characteristics of the generating stations are given by
F1 = a + bP1 + cP²1
F2 = a + b P2 + 2cP²2
Where P1 and P2 are the generation in MW of G1 and G2, respectively. For most economic generation to meet 300 MW of load, P1 and P2 respectively, are
Given that
P1 + P2 = 200 MW
Optimum condition of economic load dispatch is
Ic1 = Ic2
b + 2cP1 = b + 4cP2
2cP1 = 4cP2
P1 = 2P2
Therefore, P1 = 200 MW and P2 = 100 MW
08․ The power generated by two plants are;
P1 = 50 MW, P2 = 40 MW. If the loss coefficients are B11 = 0.001, B22 = 0.0025 and B12 = -0.0005, then power loss will be
Power loss of a transmission line
PL = B11×P²1 + B22×P²2 + 2×B12×P1×P2
Where,
B11,B22,B12 and B21 are B coefficients
P1 and P2 are power delivered by generating stations.
Given that,
P1 = 50 MW, P2 = 40 MW
B11 = 0.001, B22 = 0.0025 and B12 = -0.0005
By substituting the above values,
Power loss = 4.5 MW
09․ If, for a given alternator in economic operation mode, the incremental cost is given by (0.012 P + 8) Rs/MWh, dPL/dP = 0.2 and plant λ = 25, then power generation is
Given that,

10․ The economics of power plant is greatly influenced by
Plant load factor is defined as the ratio of average power generation to the maximum power generation.
Plant load factor = Average power/ Maximum power
Therefore, ideal plant load factor is one and practical load factor is less than 1.
Diversity factor is defined as the ratio of sum of individual maximum demand to the station maximum demand.
Diversity factor = Sum of individual maximum demand/ Station maximum demand
Both load factor and diversity factor depends on maximum demand. Therefore, economics of power plant is greatly influenced by both load factor and diversity factor.
<<<2425262728>>>

