Temperature Rise Test of Transformer

A temperature rise test of a transformer is an important test which should be included in any type test of an oil transformer. In this test, we check whether the temperature rising limit of the transformer winding and transformer oil is as specified by the manufacturer.

Temperature Rise Test for Top Oil of Transformer

  1. First, the LV winding of the transformer is short-circuited.
  2. Then one thermometer is placed in a pocket in the transformer top cover. Other two thermometers are placed at the inlet and outlet of the cooler bank respectively.
  3. The voltage of such value is applied to the HV winding that power input is equal to no load losses plus load losses corrected to a reference temperature of 75oC.
  4. The total losses are measured by three wattmeters method.
  5. During the test, hourly readings of top oil temperature are taken from the thermometer already placed in the pocket of the top cover.
  6. Hourly readings of the thermometers placed at inlet and outlet of the cooler bank are also noted to calculate the mean temperature of the oil.
  7. Ambient temperature is measured by means of a thermometer placed around the transformer at three or four points situated at a distance of 1 to 2 meter from and half-way up the cooling surface of the transformer.
  8. Temperature rise test for top oil of transformer should be continued until the top oil temperature has reached an approximate steady value that means testing would be continued until the temperature increment of the top oil becomes less than 3oC in one hour. This steady value of the top oil is determined as the final temperature rise of transformer insulating oil.
oil temperature rise test
  1. There is another method of determination of oil temperature. Here the test is allowed to be continued until the top oil temperature rise does not vary more than 1oC per hour for four consecutive hours. The loweest reading during this time is taken as the final value for the temperature rise of the oil.
oil temperature rise

During temperature rise test for top oil of transformer, we short-circuit the LV winding and apply a voltage to the HV winding. So for full load rated current flows in the transformer, the supply voltage required will much less than rated transformer voltage. We know that the core loss of a transformer depends upon voltage. So there will not be any considerable core losses occurring in the transformer during this test. But for getting an actual temperature rise in the transformer oil, we have to compensate for the lack of core losses by additional copper loss in the transformer. To make up for these losses, transformer’s draw much more current from a source than the transformer’s rated value.

Temperature rise limits of transformer when it is oil immersed, given in the table below

 Temperature rise limit
for air as
cooling medium
Temperature rise limit
for water as
cooling medium
Condition
Winding55oC60oCWhen oil circulation is natural

 

60oC65oCWhen oil circulation is forced

 

Top Oil50oC55oCWhen transformer is sealed &
equipped with conservator tank
45oC50oCWhen transformer is neither sealed
nor equipped with conservator tank

NB: These temperature rises limits mentioned in the above table are the temperature rise above the temperature of cooling medium. That means these are the difference between winding or oil temperature and temperature of cooling air or water.

Winding Temperature Rise Test on Transformer

  1. After completion of temperature rise test for top oil of transformer the current is reduced to its rated value for transformer and is maintained for one hour.
  2. After one hour the supply is switch off and short circuit and supply connection to the HV side and short circuit connection to the LV side are opened.
  3. But, the fans and pumps are kept running (if any).
oil temperature rise
  1. Then resistance of the windings are measured quickly.
  2. But there is always a minimum 3 to 4 minutes time gap between first measurement of resistance and the instant of switching off the transformer, which can not be avoided.
  3. Then the resistances are measured at the same 3 to 4 minutes time intervals over a period of 15 minutes.
  4. Graph of hot resistance versus time is plotted, from which winding resistance (R2) at the instant of shut down can be extrapolated.
  5. From this value, θ2, the winding temperature at the instant of shut down can be determined by the formula given below-

    Where, R1 is the cold resistance of the winding at temperature t1.

For determining winding temperature rise we have to apply the above discussed indirect method. That means hot winding resistance is measured and determined first and then from that value we have to calculate the winding temperature rise, by applying resistance temperature relation formula. This is because unlike oil the winding of transformer is not accessible for external temperature measurement.

   
Want To Learn Faster? 🎓
Get electrical articles delivered to your inbox every week.
No credit card required—it’s 100% free.

About Electrical4U

Electrical4U is dedicated to the teaching and sharing of all things related to electrical and electronics engineering.

1 thought on “Temperature Rise Test of Transformer”

Leave a Reply to Electrical4U Cancel reply